Frequency of Maintenance Tests
NETA recognizes that the ideal maintenance program is reliability-based, unique to each plant and to each piece of equipment. In the absence of this information and in response to requests for a maintenance timetable, NETA’s Standards Review Council presents the following time-based maintenance schedule and matrix.
One should contact a NETA Full-Member company for a reliability-based evaluation.
The following matrix is to be used in conjunction with NETA’s Frequency of Maintenance Tests table. Application of the matrix is recognized as a guide only.
Specific
condition, criticality, and reliability must be determined to correctly apply
the matrix. Application of the matrix, along with the culmination of
historical testing data and trending, should provide a quality electrical
preventive maintenance program.
|
MAINTENANCE
FREQUENCY MATRIX |
||||
|
|
EQUIPMENT
CONDITION |
|||
|
POOR |
AVERAGE |
GOOD |
||
|
EQUIPMENT
RELIABILITY REQUIREMENT |
LOW |
1.0 |
2.0 |
2.5 |
|
MEDIUM |
0.50 |
1.0 |
1.5 |
|
|
HIGH |
0.25 |
0.50 |
0.75 |
|
APPENDIX B (cont.)
Inspections
and Tests (Frequency
in Months) Multiplier for Inspections and Tests (Multiply
Value by Matrix) |
||||
|
Section |
Description |
Visual |
Visual & Mechanical |
Visual & Mechanical & Electrical |
|
7.1 |
Switchgear
& Switchboard Assemblies |
12 |
12 |
24 |
|
7.2 |
Transformers |
|||
|
7.2.1.1 |
Small
Dry-Type Transformers |
2 |
12 |
36 |
|
7.2.1.2 |
Large
Dry-Type Transformers |
1 |
12 |
24 |
|
7.2.2 |
Liquid-Filled
Transformers |
1 |
12 |
24 |
|
|
Sampling |
- |
- |
12 |
|
7.3 |
Cables |
|||
|
7.3.2 |
Low-Voltage
Cables |
2 |
12 |
36 |
|
7.3.3 |
Medium-
and High-Voltage Cables |
2 |
12 |
36 |
|
7.4 |
Metal-Enclosed
Busways |
2 |
12 |
24 |
|
|
Infrared
Only |
- |
- |
12 |
|
7.5 |
Switches |
|
|
|
|
7.5.1.1 |
Low-Voltage
Air Switches |
2 |
12 |
36 |
|
7.5.1.2 |
Medium-Voltage
Metal-Enclosed Switches |
- |
12 |
24 |
|
7.5.1.3 |
Medium-
and High-Voltage Open Switches |
1 |
12 |
24 |
|
7.5.2 |
Medium-Voltage
Oil Switches |
1 |
12 |
24 |
|
7.5.3 |
Medium-Voltage
Vacuum Switches |
1 |
12 |
24 |
|
7.5.4 |
Medium-Voltage
SF6 Switches |
1 |
12 |
24 |
|
7.5.5 |
Cutouts
|
12 |
24 |
24 |
|
7.6 |
Circuit
Breakers |
|||
|
7.6.1.1 |
Low-Voltage
Insulated-Case/Molded-Case CB |
1 |
12 |
36 |
|
7.6.1.2 |
Low-Voltage
Power CB |
1 |
12 |
36 |
|
7.6.1.3 |
Medium-Voltage
Air CB |
1 |
12 |
36 |
|
7.6.2.1 |
Medium-Voltage
Oil CB |
1 |
12 |
36 |
|
|
Sampling |
- |
- |
12 |
|
7.6.2.2 |
High-Voltage
Oil CB |
1 |
12 |
12 |
|
|
Sampling |
- |
- |
12 |
|
7.6.3.1 |
Medium-Voltage
Vacuum CB |
1 |
12 |
24 |
|
7.6.4.1 |
Extra-High-Voltage
SF6 |
1 |
12 |
12 |
|
7.7 |
Circuit
Switchers |
1 |
12 |
12 |
|
7.8 |
Network
Protectors |
12 |
12 |
24 |
|
APPENDIX B (cont.) Inspections and Tests (Frequency
in Months) Multiplier for Inspections and Tests (Multiply
Value by Matrix) |
||||
|
Section |
Description |
Visual |
Visual & Mechanical |
Visual & Mechanical & Electrical |
7.9 |
Protective
Relays |
|||
|
|
Electromechanical |
1 |
12 |
12 |
|
|
Electronic |
1 |
12 |
12 |
|
7.10 |
Instrument
Transformers |
12 |
12 |
36 |
|
7.11 |
Metering
Devices |
12 |
12 |
36 |
|
7.12 |
Regulating
Apparatus |
|||
|
7.12.1.1 |
Step-Voltage
Regulators |
1 |
12 |
24 |
|
|
Sample
Liquid |
- |
- |
12 |
|
7.12.1.2 |
Induction
Regulators |
12 |
12 |
24 |
|
| ||||